Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM03212
Parcel: 133180080

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03212
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide vent piping of sufficient size to comply with Section 904.1, UPC 2006. Vents located upstream from pumps, ejectors, grease interceptors, backwater valves, or other devices that obstruct the free flow of gases between the building sewer and the outside atmosphere shall not be used for meeting the required cross-sectional vent area.
11/21/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide support details and structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the relocation of the existing grease hood. Reference: Section 302.1, IMC 2006.
2. Show the limits of the roof to verify that the heat pumps being replaced on the roof have adequate maintenance access. Reference: Section 306.1, IMC 2006.
3. Provide the listing information for the new Type I kitchen hood. Reference: Sections 106.3.1and 507.1, IMC 2006
11/21/2008 ROBERT SHERRY WATER REVIEW Approved
11/26/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/09/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
12/09/2008 SUE REEVES REJECT SHELF Completed