Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM03212
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/21/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide vent piping of sufficient size to comply with Section 904.1, UPC 2006. Vents located upstream from pumps, ejectors, grease interceptors, backwater valves, or other devices that obstruct the free flow of gases between the building sewer and the outside atmosphere shall not be used for meeting the required cross-sectional vent area. |
11/21/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Provide support details and structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the relocation of the existing grease hood. Reference: Section 302.1, IMC 2006. 2. Show the limits of the roof to verify that the heat pumps being replaced on the roof have adequate maintenance access. Reference: Section 306.1, IMC 2006. 3. Provide the listing information for the new Type I kitchen hood. Reference: Sections 106.3.1and 507.1, IMC 2006 |
11/21/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/26/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/09/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
12/09/2008 | SUE REEVES | REJECT SHELF | Completed |