Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2008 GERRY KOZIOL WWM REVIEW Approved
10/21/2008 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T08CM03193

10/24/08 1428 N. EUCLID AVE.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


SITE PLAN:

1. PLEASE PROVIDE FOR THE INCLUSIVE HOME ENTRANCE. WITH THE STEPS ,WILL THE ENTRANCE BE POSSIBLE?

FOUNDATION PLAN:

1. PROVIDE AN ACCESSIBLE ENTRANCE. INCLUSIVE HOME DESIGN SECTION 1003.3 AND 303.1 .

2. SHEAR PANEL SCHEDULE ; SIMPSON PAHD DOESN'T HAVE 1800# TINSILE STRENGTH UNLESS IT'S 8" FROM THE CORNER (END DISTANCE) OF THE FOUNDATION. THE HOLD-DOWNS ARE REQUIRED ON THE END STUD OF THE PANEL AND TO BE RATED AT 1800#. DID YOU MEAN "HPAHD22"? R602.10.6.1 AND TABLE 602.10.6 .

FLOOR PLAN:

1. SHEAR PANEL SCHEDULE ; SEETHE SHEAR PANEL SCHEDULE NOTES ON THE FOUNDATION SECTION.

2. WILL THE ATTIC ACCESS HAVE 30" OF HEAD ROOM OVER THE OPENING ? R807

STRUCTURAL PLANS:

1. PROVIDE MANUFACTURER'S DATA FOR PRE-FAB TRUSSES. TRUSS DATA MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN
ARIZONA. TRUSS DATA SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS.

2. DETAIL GABLE END BRACING CONNECTIONS.

ELEVATIONS:

1. FRONT ELEVATION ; THE WINDOW SILL AND SHUTTER ARE INDICATED AS FASCIA.


SECTIONS - DETAILS - MISC. NOTES:

1. 2/5 ; HOW WILL THE EPS (WHITE FOAM BOARD) IN THE GABLE BE SEPARATEDFROM THE INTERIOR OF THE BUILDING? R314.4 SEE ALSO R314.5.3

2. ROOF VENTILATION CALCS. / 6 ; THE INTERGOVERNMENTAL AGREEMENT BETWEEN THE CITY AND OTHER JURISDICTIONS DOESN'T INCLUDE COMPOSITION SHINGLES. IRC SECTION 806.4 ALLOWS NON VENTED ATTICS WITH SOME CONDITIONS. PLEASE SPECIFY THE INSULATION AND NOTE THE ABSENCE OF A "VAPOR RETARDER". R806.4

PLUMBING PLAN:

1. PLUMBING NOTE 10 / 9 ; PLEASE INCLUDE ALL QUICK-ACTING VALVES IN THE NOTE REQUIRING WATER HAMMER PROTECTION, i.e. FLUSH VALVES AND REFRIGERATOR WATER CONNECTIONS. UPC SECTION 609.10 .

ELECTRICAL PLANS:

1. PLEASE ENSURE THE KITCHEN ISLAND TOP DOESN'T OVERHANG THE TWO RECEPTACLES ON CIRCUIT 23 BY MORE THAN 6". E3809.4.5 EXCEPTION .


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 837-4910