Permit Number: T08CM03185
Parcel: 124080430

Address:
1302 E 9TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03185
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 12-10-08
Activity: T08CM03185 2nd review
Address: 1302 E 9th St.
Applicant: Bas-Isaac / Latcham

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

2. Provide legible text minimum 1/8" per Development Standards or submit an appeal to the Building Official.

MECHANICAL PLAN:
3. Provide combustion air vents for all fuel-gas appliances, M1702.2. The minimum size openings for combustion air vents is greater than or equal to 1 square inch per 4,000 Btu. Based on the information provided, each vent would need a minimum of 40 square inches, M1703.2.1.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status