Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T08CM03172
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/04/2008 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS T08CM03172 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html GENERAL NOTES: " All code references to the International Residential Code shall be changed from 2003 to 2006 with appropriate paragraph references. Revise unrecognized code references on sheet 2 & 5. " Interior alterations require the installation of smoke alarms at existing bedrooms, R313.2.1. SITE PLAN: 1. Indicate the location of utility meters, R106.1.1. Clarify the electrical service Keynote 3 on the Sire Plan. FOUNDATION PLANS: 1. Show or note an 8" minimum separation of untreated exterior framing above finished grade for the Storage Building, R319.1 item 2 2. Show a Storage Building tie-down detail for accommodating lateral wind loading, R401.2. 3. Framed exterior walls of enclosed roof structures require continuous concrete footings of minimum 12" width and 12" below undisturbed ground surface, R403.1. Show Foundation Keynote 3 and locate foundation on the plan for the new Dining and Kitchen walls. FLOOR PLANS: 1. Each detached (non-rated) structure requires a separate 3-foot fire separation distance. One structure requires not less than one-hour fire-resistive construction (without openings) if placed less than six feet from an existing building, R302.1. Show compliance with R302.1 (City of Tucson Amended) by providing a section detail of materials prescribed in IBC Table 720.1(2), Items 15-1.1 to 16-1.3. STRUCTURAL PLANS: 1. Show all new exterior load-bearing walls on the Floor Plan and Framing Plan, R106.1.1. Show Framing Plan Keynote 7 for the new Dining wall between post and corner as load-bearing (Keynote 2 or 6). This is shown as a load-bearing wall with a header for a window opening. 2. Show load carrying connections for the rafter to wall Detail 4/3 & 4/4, R301.1. Fascia with end grain nailing to rafters will not carry roof loading. Add a load carrying ledger connected to wall studs. SECTIONS - DETAILS: 1. Clarify rafter sizes shown on Detail 1/2 consistent with Detail 1/3 and revise the insulation rating for a 5-1/2" cavity, R106.1.1. 2. Clarify the T1-11 sheathing thickness shown on Detail 1/2, 1/3 and Detail 1/4, R106.1.1. It is unnecessary to show a Detail three places. 3. Clarify Note 1 sheet 4 (18" footing depth) to be consistent wit details, R106.1.1. PLUMBING PLANS: 1. Note the relocation of the Kitchen sink to comply with the 2006 UPC. MECHANICAL PLANS: 1. Show R-4.2 insulation when ducts are located in an unconditioned space (chase) inside the thermal envelope, IECC 503.2.7 (City of Tucson Amended). 2. Show the roof mounted A/C (heat pump) with tonnage capacity referenced at Note 1 sheet 5, M1302.1. Include the return air duct size if new or installed without permit. ELECTRICAL PLANS: 1. Smoke alarms are required outside each separate sleeping area, R313.2. 2. Provide wire sizes on the panel schedule for the new circuits and show an entry for the A/C referenced at Note 1, E3304.11 & E3606.2. Indicate the location of new disconnect switches for air handling equipment on the plan, E4001.5. 3. Revise the electrical load calculation showing the total square footage (706 SF) and include the cooling (or heating) load between Total and Grand Total , E3502.2. 4. Show Living Room receptacle outlets at wall spaces 2' or more with no point along the wall (exclude door openings) more than 6' from a receptacle outlet, E3801.2. Required for new and altered (Old Kitchen) walls. 5. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations (Lighting), E3603.2 and E3801.3 through E3801.4.5. 6. Show a GFCI receptacle outlet on the same level within 25' of exterior HVAC (roof mount) equipment, E3801.11. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Both standard and high density R-30 batt insulation requires a space greater than provided with 2" x 6" framing (Details and Section A). Identify the installed value, and calculate compliance using RES check. Select the location of Pima County rather than Pima (City). "Pima, AZ: 2006 IECC <4,000 ft" is found at the end of the list for the State selection. (Do not select Arizona). If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/12/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 11/12/2008 | SUE REEVES | REJECT SHELF | Completed |