Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08CM03167
Parcel: 10712225A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03167
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/30/2008 ENEWCOM1 ADA REVIEW Denied 1. SEE BUILDING COMMENTS.
09/30/2008 JWILLIA5 ZONING HC SITE REVIEW Denied 1. SEE BUILDING COMMENTS.
10/01/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SEE COMMENTS FROM ACTIVITY #T08CM03160.
10/02/2008 DAVE MANN FIRE REVIEW Denied Please provide location(s) of new and/or existing fire hydrants, with dimensions to property lines. Refer to C.O.T. amendments to the 2006 IFC (section 508) for spacing requirements.
Verify occupancy classification with building department.
Fire department approved lock box will be required at access gate.
Please include the following design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
Define where fire sprinklers will be installed, and how they will be supplied.
Alley on west side of project does not appear to meet requirements for fire department access .
10/07/2008 GERRY KOZIOL WWM REVIEW Denied need 5th floor credit evaluation
10/09/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Comments on permit T08CM03160
10/09/2008 PAUL MACHADO ENGINEERING REVIEW Needs Review
10/14/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 2835 N Stone Avenue
T08CM03160, T08CM03161, T08CM03162, T08CM03163, T08CM03164, T08CM03165, T08CM03166, T08CM03167, T08CM03168
Building Plan (1st Review)

TRANSMITTAL DATE: October 14, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t08cm03160.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
10/14/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Provide an auxiliary drain pan or secondary drain system for HP-1. Reference: Section 307.2.3 IMC 2006.
10/14/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Clarify the source of hot water for the apartments. Reference: Section 103.2.3, UPC 2006.
3. Clarify the call-out for "2"FD-1" on the sewer/vent riser diagram; Is it BT-1 and SH-1? Reference: Section 103.2.3, UPC 2006.
4. Revise the location of the call-out for WC-1 on the sewer/vent riser diagram to avoid confusion. Reference: Section 103.2.3, UPC 2006.
5. Provide a cleanout for WC-1 located on the first floor, as shown on the sewer/vent riser diagram. Reference: Sections 707.4 and 707.11, UPC 2006.
10/14/2008 ROBERT SHERRY WATER REVIEW Denied Provide a site utility plan showing the location of the reduced pressure backflow assembly and water meter for this building and indicate the sizes of the backflow assembly and water meter. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf

Final Status

Task End Date Reviewer's Name Type of Review Description
11/03/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
11/03/2008 SUE REEVES REJECT SHELF Completed