Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM03161
Parcel: 10712225A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03161
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 2835 N Stone Avenue
T08CM03160, T08CM03161, T08CM03162, T08CM03163, T08CM03164, T08CM03165, T08CM03166, T08CM03167, T08CM03168
Building Plan (2nd Review)

TRANSMITTAL DATE: December 8, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t08cm03160.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
12/08/2008 GERRY KOZIOL WWM REVIEW Denied need 5th floor credit evaluation
12/08/2008 MARTIN BROWN FIRE REVIEW Denied Please provide location(s) of new and/or existing fire hydrants, with dimensions to property lines. Refer to C.O.T. amendments to the 2006 IFC (section 508) for spacing requirements.
Verify occupancy classification with building department.
Fire department approved lock box will be required at access gate.
Please include the following design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
Define where fire sprinklers will be installed, and how they will be supplied.
Alley on west side of project does not appear to meet requirements for fire department access .
12/08/2008 RBROWN1 ADA REVIEW Passed NOT A COT PROJECT
12/10/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SEE COMMENTS FROM ACTIVITY #T08CM03160.
12/11/2008 ERIC NEWCOMB ZONING HC SITE REVIEW Denied 1. SEE BUILDING COMMENTS.
12/18/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied SEE REMARKS FOR TO8CM03160
12/18/2008 JASON GREEN ENGINEERING REVIEW Needs Review Building plan can not be approved prior to site plan approval.

Review all comments associated with the site plan review, T08CM03039 per Paul Machado's comments dated October 8, 2008. JGreen
12/22/2008 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Needs Review
12/22/2008 CPIERCE1 WATER REVIEW Needs Review
12/22/2008 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/05/2009 THAUSER1 OUT TO CUSTOMER Completed
01/05/2009 THAUSER1 REJECT SHELF Completed