Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM03160
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/08/2008 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: 2835 N Stone Avenue T08CM03160, T08CM03161, T08CM03162, T08CM03163, T08CM03164, T08CM03165, T08CM03166, T08CM03167, T08CM03168 Building Plan (2nd Review) TRANSMITTAL DATE: December 8, 2008 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t08cm03160.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: |
| 12/08/2008 | MARTIN BROWN | FIRE | REVIEW | Denied | Please provide location(s) of new and/or existing fire hydrants, with dimensions to property lines. Refer to C.O.T. amendments to the 2006 IFC (section 508) for spacing requirements. Verify occupancy classification with building department. Fire department approved lock box will be required at access gate. Please include the following design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. Define where fire sprinklers will be installed, and how they will be supplied. Alley on west side of project does not appear to meet requirements for fire department access . |
| 12/08/2008 | RBROWN1 | ADA | REVIEW | Passed | NOT A COT PROJECT |
| 12/08/2008 | GERRY KOZIOL | WWM | REVIEW | Denied | need 5th floor credit evaluation |
| 12/08/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Needs Review | Building plan can not be approved prior to site plan approval. Review all comments associated with the site plan review, T08CM03039 per Paul Machado's comments dated October 8, 2008. JGreen |
| 12/10/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS ITEM 28: PROVIDE REFERENCE FOR SHEET S401 PLAN LOCATION. 2. SHEET A120; BUILDING PLAN: HANDICAP RESTROOMS CLEARANCE AT THE DOORS (1'-0") ON THE LATCH SIDE DOES NOT MEET ANSI FIGURE 404.2.3.4(a). FAIR HOUSING SECTION 1002.5 REFERS TO ANSI SECTION 404 FOR REQUIREMENTS. VERIFY. 3. SHEET A112; PLAN 1: HANDICAP RESTROOM CLEARANCE AT THE DOOR (1'-0") ON THE LATCH SIDE. SEE NOTE 2 ABOVE. PROVIDE VERTICAL GRAB BAR PER ANSI FIGURE 604.5.1. 4. PREVIOUS ITEM 34: ANSI SECTION 1002.12 REFERS TO ANSI SECTION 902 FOR KITCHEN COUNTER HEIGHTS. IN ADDITION, ANSI SECTION 1003.12.3.2 REQUIRES 34" COUNTER HEIGHT (OR ADJUSTABLE COUNTER). THIS REQUIREMENT ALSO APPLIES TO OTHER DINING/WORK SURFACES. 5. PREVIOUS ITEM 32: PROVIDE CLEARANCES FOR TRANSFER-TYPE SHOWER PER ANSI FIGURE 608.2.1. YOUR RESPONSE THAT THIS IS A TUB IS NOT INDICATED ON THE DRAWINGS. 6. IN GENERAL, WHEN USING THE FAIR HOUSING STANDARDS, REFER TO THE SECTION OF THAT PUBLICATION WHEN REPLYING TO REVIEW COMMENTS. 7. WRITTEN APPROVAL IS REQUIRED BY THE BUILDING OFFICIAL, JESSIE SANDERS, FOR ALL DEFERRED SUBMITTALS. |
| 12/11/2008 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 12/17/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PROJECT;T08CM03160 TI OFFICE AND UNITS DENIED FOR FOLLOWING ITEMS, PER CONVERSATION WITH ELECTRICAL ENGINEER,ALL ITEMS LISTED BELOW HAVE BEEN REVIEWED. 1. THE OUTDOOR LIGHTING CALCULATIONS ARE INCORRECT,TOTAL INSTALLED MORE THAN ALLOWED. 2.SHEET E-111 CIRCUIT A1-13 PUT IN FOR DRINKING FOUNTAIN IS BEING USED FOR WATER HEATER. 3.SHEET 310 PANEL A 1 HAS A 100 AMP PANEL BUT SHOWS A 152 AMP LOAD,THE FEEDERS ARE 100 AMP CAPACITY . 4. PROVIDE FAULT CURRENT VALUES AT SERVICE AND PANELS. RAY T MAJUTA DSD ELECTRICAL PLAN CHECK CITY OF TUCSON 12/18/08 520-837-4988 |
| 12/22/2008 | CPIERCE1 | WATER | REVIEW | Needs Review | |
| 12/22/2008 | CPIERCE1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 12/22/2008 | CPIERCE1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/05/2009 | THAUSER1 | OUT TO CUSTOMER | Completed |
| 01/05/2009 | THAUSER1 | REJECT SHELF | Completed |