Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03160
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/30/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 09/30/2008 | ENEWCOM1 | ADA | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 10/01/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PER PHONE CONVERSATION WITH ANDREW ABERNATHY ON 10-1-08, DEVELOPMENT SERVICES DEPARTMENT NEEDS TO BE ADVISED IF ACCESSIBILITY FALLS UNDER 1994 'ADA STANDARDS FOR ACCESSIBLE DESIGN' (ADAAG) OR 2003 'ICC/ANSI A117.1. 2. SHEETS T010/S102: DEFERRED SUBMITTALS REQUIRE WRITTEN APPROVAL FROM THE BUILDING OFFICIAL, JESSIE SANDERS, AND MUST ACCOMPANY DRAWINGS SUBMITTED FOR CHECKING. 3. SHEET S301; SECTIONS 102/103/104: PROVIDE ARCHITECTURAL SPECIFICATION FOR COATING STEEL BELOW GRADE. DID NOT LOCATE IN SPECIFICATIONS PROVIDED. TYPICALLY SEE CONCRETE PIER BELOW GRADE, OR ENCASING COLUMN AND BASE PLATE IN CONCRETE. VERIFY. 4. SHEET S301; SECTION 108: VERIFY NO GROUT BELOW BASE PLATE. 5. SHEET S301; SECTIONS 105/112: FOOTING REINFORCING SHOWN IN SECTIONS DIFFERS FROM REINFORCING INDICATED IN THE FOOTING SCHEDULE F4 (2-#4 CONT.). CLARIFY. 6. SHEET S301; SECTION 113: ADD BENT BAR VERTICAL TO TIE HORIZONTAL #4 @ 10" O.C. VERIFY. 7. SHEET S301; SECTION 115: ADD BENT BAR VERTICAL TO TIE HORIZONTALS? CALL OUT HORIZONTAL BAR. VERIFY. 8. SHEET S301; SECTION 116: ADD NOTES FOR SHORING/SUPPORT OF EXISTING FOUNDATION DUE TO ADDITION OF NEW FOOTING BELOW EXISTING. 9. SHEET S301; TLCP TITLE BLOCK: REVISE NOTE 'FOUNDATION DETAILS 101 THRU 120'. 10. SHEET S302; TLCP TITLE BLOCK: REVISE NOTE 'FOUNDATION DETAILS 121 THRU 140'. 11. SHEET S301; SECTION 108: ADD COLUMN TIES? VERIFY. 12. SHEET S302; SECTION 121: VERIFY NO GROUT BELOW BASE PLATE. 13. SHEET S401; TLCP TITLE BLOCK: REVISE NOTE 'FOUNDATION DETAILS 201 THRU 220'. 14. SHEET S401; SECTION 205: PLYWOOD IS NOT EXISTING. VERIFY. 15. SHEET S402; TLCP TITLE BLOCK: REVISE NOTE 'STAIR FRAMING DETAILS 221 THRU 240'. 16. SHEET S403; TLCP TITLE BLOCK: REVISE NOTE 'ROOF FRAMING DETAILS 241 THRU 260'. 17. SHEET S202: NORTH ARROW INCORRECT. 18. SHEET S302; SHEET S211: VERIFY SECTION 122/122A. ARE THESE CORRECT? 19. SHEET S402; DETAIL 224A: NOTE 'NO BEAM AT DETAIL A' IS CONFUSING. BEAM IS INDICATED ON PLAN. CLARIFY. 20. SHEET S403; TLCP TITLE BLOCK: REVISE NOTE 'ROOF FRAMING DETAILS 241 THRU 260'. 21. SHEET S222; DETAIL 222A: SECTION MAKES NO REFERENCE TO CONDITION 'A'. CLARIFY. 22. SHEET S232: SECTION CUT 222 AT SOUTH FRAMING SHOULD BE 222A? VERIFY. 23. SHEET S241; RAMADA/VENDING FOUNDATION PLANS: INDICATE ON MAIN FOUNDATION PLAN WHERE THESE TWO AREAS OCCUR. 24. SHEET S242; RAMADA/VENDING FOUNDATION PLANS: SEE NOTE 23. 25. SHEET S241; FOUNDATION PLAN: PROVIDE NOTE TO REFERENCE HOLDOWN INDICATIONS TO SCHEDULE ON S104. 26. SHEET S242; TLCP TITLE BLOCK: REVISE NOTE 'SEE S501 SHEETS FOR DETAILS'. 27. SHEET S404; TLCP TITLE BLOCK: REVISE NOTE 'ROOF FRAMING DETAILS 261 THRU 280'. 28. SHEET S401; PARTIAL FLOOR FRAMING PLAN: PROVIDE REFERENCE FOR THIS PLAN LOCATION. 29. SHEET A112; HANDICAP RESTROOM: PROVIDE DIMENSIONED ELEVATIONS PER APPROPRIATE CODE. 30. SHEET A112; HANDICAP RESTROOM: PROVIDE WATER CLOSET CLEARANCES PER APPROPRIATE CODE. 31. SHEET A112; HANDICAP RESTROOM: PROVIDE MANEUVERING CLEARANCE AT BATH ENTRANCE PER APPROPRIATE CODE. 32. SHEET A112; HANDICAP RESTROOM: PROVIDE SIZE/CLEARANCE/CONFIGURATION FOR TRANSFER TYPE SHOWER PER APPROPRIATE CODE. 33. SHEET A113; HANDICAP RESTROOM: SEE ITEMS 29 THROUGH 32. CHANGE LEVEL INDICATIONS (2/3). 34. GENERAL: IN ACCESSIBLE UNITS, MAKE SURE COUNTER/WORK AREA HEIGHTS MEET APPROPRIATE CODE REQUIREMENTS. 35. SHEET A120; ACCESSIBLE RESTROOMS: PROVIDE DIMENSIONED PLANS/ELEVATIONS/CLEARANCES PER APPROPRIATE CODE. 36. GENERAL: PROVIDE LARGE SCALE DIMENSIONED PLANS OF ALL ACCESSIBLE RESTROOMS. PROVIDE DIMENSIONED ELEVATIONS OF RESTROOMS. PROVIDE TURNING/FIXTURE CLEARANCES. |
| 10/02/2008 | DAVE MANN | FIRE | REVIEW | Denied | Please provide location(s) of new and/or existing fire hydrants, with dimensions to property lines. Refer to C.O.T. amendments to the 2006 IFC (section 508) for spacing requirements. Verify occupancy classification with building department. Fire department approved lock box will be required at access gate. Please include the following design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. Define where fire sprinklers will be installed, and how they will be supplied. Alley on west side of project does not appear to meet requirements for fire department access . |
| 10/06/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). 2. Provide calculations to show how adequate ventilation was determined for the areas served by RTU-2. Reference: Sections 403.3 and 403.3.2, IMC 2006. 3. Ventilation for restrooms in public spaces requires a minimum of 75 CFM of mechanical exhaust per water closet or urinal. Reference: Table 403.3, IMC 2006. 4. Clarify the routing and termination of the condensate from HP-1 and the HP-5 located in room R30. Reference: Sections 106.3.1 and 307.2.1, IMC 2006. 5. Clarify the location of HP-6; is it mislabeled as HP-5? Reference: Section 106.3.1, IMC 2006. 6. Provide an auxiliary drain pan or secondary drain system for HP-1. Reference: Section 307.2.3 IMC 2006. |
| 10/06/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the minimum plumbing facilities (e.g. a drinking fountain for the office area) required by Table 2902.1 and Section 2902.2, IBC 2006, for a business occupancy. 2. Provide the total connected load for the gas meter serving this building, the pipe size(s), and the developed pipe length. Reference: Section 1209.1, UPC 2006. |
| 10/06/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide a site utility plan showing the location of the reduced pressure backflow assembly and water meter for this building and indicate the sizes of the backflow assembly and water meter. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf |
| 10/07/2008 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Denied | 1. SEE 'BUILDING' COMMENTS. |
| 10/07/2008 | GERRY KOZIOL | WWM | REVIEW | Denied | need 5th floor credit evaluation |
| 10/09/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PROJECT;2835 N STONE AV T08CM03160 T I Office and Units This project has been denied for the following items,provide response for items and indicate actions taken to resolve them. 1.Provide calculations for compliance to the 2005 City of Tucson/Pima County Outdoor Ord # 10135 for all outdoor lighting. 2.Provide Interior Lighting load calculations per the 2006 IECC code requirements for multi-family structures. 3.Sheet E000,circuits used for outdoor receptacles, lights and the motorized gate do not match with those in the panel schedules. 4.Provide load calculations for individual panels, one for each type of unit. 5.Water heater disconnects to have proper clearance for access, please note on plan. 6.Some units do not comply with 2005 NEC 210-52 H 2 for receptacle spacing, any wall space wider than two feet requires one. 7.Sheet E310 Panel A 1 shows a 100amp CB, however on panel SE B on sheet E410 it shows a 150amp CB. 8.Indicate on all Service Entrance Panels they are to Have a 400 amp Main CB. 9.Sheet E410 Panelboard SE B shows two feeders to panels marked J 1 , on Service One Line Diagram Sheet E310 they are marked J210 and J211, please mark the same. 10.Sheet E410 Panel SE B shows an extra J110 not in Panel SE B. 11.Provide fault current calculations at service and at individual panels. 12.Sheet E313 on Service Entrance H calculations the sq footage of 411 is used twice with different values one is 1.2kva the other is 2.3kva. 13.ther are no note or specfications on wiring methods, however on some references conductors are required to be in conduits, will this job be required to be in conduit? 14.SWince there is only one set of plans for this job all comments on this page refer to all buildings and permits. Ray T Majuta DSD City of Tucson Elect Plan Ck 520-837/4988 10/11/08 |
| 10/09/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | |
| 10/14/2008 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: 2835 N Stone Avenue T08CM03160, T08CM03161, T08CM03162, T08CM03163, T08CM03164, T08CM03165, T08CM03166, T08CM03167, T08CM03168 Building Plan (1st Review) TRANSMITTAL DATE: October 14, 2008 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t08cm03160.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/03/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 11/03/2008 | SUE REEVES | REJECT SHELF | Completed |