Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM03139
Parcel: 103090670

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03139
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/09/2008 DAVE MANN FIRE REVIEW Approved
10/09/2008 GERRY KOZIOL WWM REVIEW Approved