Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T08CM03137
Parcel: 126210170

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03137
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2008 DAVE MANN FIRE REVIEW Denied Fire sprinklers required. Low fire flow available in this area, fire flow calculation area exceeds 3600 sq. ft. Refer to 2006 IFC, appendix B,Section B104, B105.
12/12/2008 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T08CM03137 Rev 12-15-08

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

STRUCTURAL PLANS:

1. Provide manufacturer's calculations and data for pre-engineered trusses with appropriate spans for accommodating the Roof Framing Plan, R106.1. Notate the Trusses Plans for supporting the size and weight of attic or roof mounted equipment, M1401.

PLUMBING PLANS:

1. Provide an accurate manufacturer's specification BTU rating.
2. Provide gas pipe sizes in compliance with connected demand, IRC G2413.3 & Table G2413.4(1).

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Show consistent placement of ceiling insulation, N1102.1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/16/2008 GERARDO BONILLA OUT TO CUSTOMER Completed