Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2008 RBROWN1 ADA REVIEW Passed NOT A COT PROJECT
09/18/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
09/19/2008 MARTIN BROWN FIRE REVIEW Approved
09/19/2008 STEVE SHIELDS ZONING REVIEW Approved
09/22/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PLEASE INCLUDE SOILS REPORT REFERENCED ON THE DRAWINGS.
2. 1/8" LETTERING IS REQUIRED ON ALL DRAWINGS UNLESS A WRITTEN APPEAL IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY THE DRAWINGS SUBMITTED FOR CHECKING.
3. SHEET CS; NOTE 4 IN GENERAL NOTES: ARE THERE ANY STORAGE RACKS IN THIS PROJECT? IF SO, ANYTHING OVER 12' IN HEIGHT REQUIRES STRUCTURAL CALCULATIONS.
09/24/2008 SUE REEVES COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/03/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/03/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/03/2008 ROBERT SHERRY WATER REVIEW Approved
10/07/2008 GERRY KOZIOL WWM REVIEW Approved
10/14/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project:7150 E Broadway Bl
Walmart Garden Remodel
T08CM03132

This project has been denied for the following items, please provide response to individual items and indicate actions to resolve them.

1.Provide panel schedule and load calculations for panel HR--existing and new loads.Also show lighting circuits for this project on this panel.
2.Provide fault current values at panels HR and LGC.
3.Rather than allow the contractor to find nearest available location for circuit connection,please provide one for circuits being added and show on plan.

Ray T Majuta
DSD City if Tucson
Electrical Plan Ck
520-837/4988
10/14/08