Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T08CM03124
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/30/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/15/2008 | CLAYTON TREVILLYAN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS Date: 10-15-08 Activity: T08CM03124 Address: 10061 E. Prairie Dog Lane Applicant: Rick Herrington Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval. GENERAL REQUIREMENTS: 1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. 2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. FLOOR PLANS: 3. Exterior walls with a fire separation distance less than 3 feet shall have not less than a one-hour fire-resistive rating with exposure from both sides. Projections shall not extend to a point closer than 2 feet from the line used to determine the fire separation distance. Projections extending into the fire separation distance shall have not less than one-hour fire-resistive construction on the underside, 2006 Amendment R302.1. 4. Specify fiber-cement board backing at tub/shower enclosure space, R702.4.2. FOUNDATION PLANS: 5. Define the extent of the masonry stem wall on the foundation plan. ELEVATIONS: 6. Provide an attic space ventilation calculation consistent with, R806.2 (1:150 ventilation or meet the exception criteria). SECTIONS - DETAILS: 7. Provide uplift resistance for roof framing (porch rafter connection to beam), R802.11.1. PLUMBING PLAN: 8. Clarify which plumbing standard will be utilized on this project and design accordingly (2006 UPC, 2003 UPC, and the 2006 IRC have all been specified). 9. Provide note requiring that water hammer arrestors be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, UPC 609.10. 10. Include all fixtures on the property in the fixture unit schedule, including existing, UPC Tables 6-5 and 7-3 (only one laundry group specified, bar sink not listed). 11. Provide the maximum developed length of water line from the meter the furthest appliance served, and the diameter of the water supply line, UPC Table 6-6. Note: The Tucson Water policy adopted 3/2/07 limits the maximum demand for a 5/8" water meter (there are no ¾" meters for Tucson Water service) to 10GPM, confirm with Tucson Water that the existing meter will be able to meet the new water demand. 12. Specify the location of the connection for the new building to the water supply system. 13. Include Fireplace #1 on the gas line schematic. 14. Provide a gas supply line sized for the proposed demand, UPC 1217.0 Table 12-8. MECHANICAL PLAN: 15. Show supply and return air ducts with a minimum R-8 insulation, R1103.2.1. 16. Specify the size and location of the furnace flue. OUTDOOR LIGHTING CODE 17. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style). Note: flood style lighting is not considered fully shielded. If you have any questions please contact: Clayton Trevillyan 520.837.4913 Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/30/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |