Permit Number: T08CM03108
Parcel: 10406011E

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM03108
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide make up air for the paint booth
09/16/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/16/2008 STEVE SHIELDS ZONING REVIEW Approved
09/16/2008 ROBERT SHERRY WATER REVIEW Approved
09/18/2008 MARTIN BROWN FIRE REVIEW Approved
09/24/2008 GBONILL1 ENGINEERING REVIEW Needs Review
09/24/2008 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review PROJECT;#T08CM03108
2075 W GARNER LANE #133

PROVIDE THE FOLLOWING.
1.HAVE ELECTRICAL ENGINEER CLEARLY RESTAMP PLANS AND DATE.
2.PPROVIDE A SERVICE ONE LINE SHOWING SERVICE AND LOAD CALCULATIONS.
3.SIZE CONDUCTORS FOR BRANCH CIRCUIT FOR PAINT BOOTH.
4.PROVIDE DOCUMENTATION ON PAINT BOOTH VERIFING LISTING BY A NTRL.


RAY T MAJUTA
DSD PLANS EXAMINER
CITY OF TUCSON
520-837/4988
9/16/08
09/24/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
09/24/2008 RONALD BROWN ZONING HC SITE REVIEW Passed
09/24/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
09/24/2008 RBROWN1 ADA REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/24/2008 GERARDO BONILLA OUT TO CUSTOMER Completed