Permit Number: T08CM03090
Parcel: 11012007B

Address:
5151 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03090
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2008 MARTIN BROWN FIRE REVIEW Approved
09/17/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEETS GSN-1/2: REDUCE GENERAL NOTES TO THOSE PERTAINING TO THIS PROJECT.
2. PROVIDE WALL/WALL FOOTING CALCULATIONS.
09/18/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 5151 E. Grant
T08CM03090
Cell Tower (1st Review)

TRANSMITTAL DATE: September 19, 2008

1. The Cell Tower plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The plan must be stamped by the Special Exception Section prior to approval by zoning.

3. Zoning acknowledges receipt of the letter from Albert Elias, AICP, Director, Urban Planning and Design, dated July 1, 2008. The following conditions need to be met or a note added to the site plan:
a. The generator will be enclosed within a sound-attenuation enclosure designed to mitigate the operation sound level.
b. Add a note to the plan stating "THE GENERATOR CAN BE RUN UP TO 45 MINUTES PER WEEK FOR TESTING AND DIAGNOSTICS."
c. Add a note to the plan stating "TESTING OF THE GENERATOR SHALL OCCUR BETWEEN THE HOURS OF 8:00 AM AND 6:00 PM."
d. Add a note to the plan stating "GENERATOR OPERATIONS SHALL COMPLY WITH SECTION 16-31 EXCESSIVE NOISE, OF THE TUCSON CITY CODE."
e. The generator site must be provided with a catchment designed to contain and hold at least 210 gallons of diesel fuel, in the event of a fuel leak.

4. Zoning will re-review the Cell Tower plan on the next submittal to insure compliance with the approved Special Exception process. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\celltower\t08cm03090.doc
09/19/2008 ROBERT SHERRY WATER REVIEW Passed
09/19/2008 SREEVES1 WWM REVIEW Passed
10/09/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/30/2008 DELMA ROBEY OUT TO CUSTOMER Completed
10/30/2008 SUE REEVES REJECT SHELF Completed