Permit Number: T08CM03062
Parcel: 10713217A

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING-WALKTHRU

Permit Number - T08CM03062
Review Name: RESIDENTIAL BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2009 MICHAEL ST. PAUL ZONING REVIEW Denied CDRC TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T08CM03062
2626 North Estrella Avenue
Addition to SFR, Shed, Ramada & Awning to 2nd Unit


TRANSMITTAL: February 9, 2009


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO).


The site is located in the R-2 Zone (LUC Section 3.25.2.A.2). The Development Designator is "K" (LUC Section 3.2.6.4.C). The Perimeter Yard Indicator is BB (LUC Section 3.2.6.4). A DDO is required for both the front yard setback and the north side-yard setback.

The minimum setback for the front yard is the greater of twenty (20) feet or one and one-half (1 ½) the height of the structure's wall facing the front property line (LUC Section 3.2.6.5.A). The required setback is twenty (20) feet. The proposed front setback is twelve (12) feet six (6) inches.

The minimum setback to the north property line is the greater of six (6) feet or two-thirds (2/3) the height (H) of each structure's wall facing the property line. The required setback for the shed is six (6) feet. The proposed setback is zero. The required setback for the Ramada, which measures twelve (12) feet, is eight (8) feet. The proposed setback is four (4) feet.

The awning on the second unit does not require a DDO. A permit may be required for each structure.
02/09/2009 MICHAEL ST. PAUL NPPO REVIEW Passed
06/01/2009 CPIERCE1 ENGINEERING REVIEW Needs Review
06/01/2009 CPIERCE1 BUILDING-RESIDENTIAL REVIEW Needs Review