Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03030
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/09/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
09/09/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide duct insulation per Section 503.2.7, IECC 2006. Reference Section 501.2, IECC 2006, as amended by the City of Tucson. |
09/09/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM03030 9/9/08 1. Sign circuit shall be counted as 1200VA per NEC 220.14 (F). At 125% this would be 1500VA, not 1000. 2. It does not appear that the Code-required 200 VA per LF has been accounted for on the Show Window circuit. Reference NEC 220.14 (G). 3. Power Plan shows receptacles on A-16,18. No such circuits on this 12-ckt panel. 4. Demonstrate compliance with the IECC. 5. Exit lighting shall comply with NEC 700.12. |
09/09/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/09/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/09/2008 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
09/09/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
09/09/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
09/09/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
09/09/2008 | ENEWCOM1 | ADA | REVIEW | Passed | |
09/09/2008 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
09/16/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |