Permit Number: T08CM03018
Parcel: 12613008D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03018
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/05/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
09/08/2008 DAVID RIVERA ZONING REVIEW Approved
09/08/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/08/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM03018 9/8/08

1. When Phase B is added, the total is 26232 VA, not 17661, for a high phase current of 219A. Please clarify this calculation, which appears to include a split breaker on Ckt 17.
2. A 5-HP motor, which would have a current of 16.7A, could have (16.7) (2.25) = 37.6 AF as an absolute maximum. Understood that the circuit breaker is properly sized further upstream, but rating the fuse at 40A may achieve the intent. Please clarify, willing to discuss.
09/08/2008 ROBERT SHERRY WATER REVIEW Approved
09/08/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/08/2008 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
09/08/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/08/2008 ENEWCOM1 ADA REVIEW Passed
09/08/2008 ERIC NEWCOMB ZONING HC SITE REVIEW Passed
09/09/2008 CAGUILA1 FIRE REVIEW Needs Review
09/09/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review