Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03018
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/05/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 09/08/2008 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 09/08/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/08/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM03018 9/8/08 1. When Phase B is added, the total is 26232 VA, not 17661, for a high phase current of 219A. Please clarify this calculation, which appears to include a split breaker on Ckt 17. 2. A 5-HP motor, which would have a current of 16.7A, could have (16.7) (2.25) = 37.6 AF as an absolute maximum. Understood that the circuit breaker is properly sized further upstream, but rating the fuse at 40A may achieve the intent. Please clarify, willing to discuss. |
| 09/08/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/08/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/08/2008 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 09/08/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/08/2008 | ENEWCOM1 | ADA | REVIEW | Passed | |
| 09/08/2008 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Passed | |
| 09/09/2008 | CAGUILA1 | FIRE | REVIEW | Needs Review | |
| 09/09/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |