Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T08CM02995
Parcel: 12306128A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02995
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 10-23-08
Activity: T08CM02995 2nd review
Address: 2301 E Drachman St.
Applicant: Kevin Osborn

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

3. Due to the extent of demolition associated with this project, the building will be required to meet the Inclusive Home Design Ordinance. Include all applicable notes needed to comply.

STRUCTURAL PLANS:
4. The existing 2x6 roof framing members are insufficient for the proposed design, R801.2.
5. Provide a continuous rafter tie at the ceiling line in order to meet the requirements of R802.3.1.
6. Provide collar ties within the top 1/3 of the roof per R802.3.1.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/30/2008 CPIERCE1 OUT TO CUSTOMER Completed
10/30/2008 SUE REEVES REJECT SHELF Completed