Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T08CM02990
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/26/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/01/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise (i.e. cloud) the plumbing drawings to show the extent of the changes made with this revision. Reference: Section 103.2.3, UPC 2006. 2. Revise the grease interceptor calculation to include the additional fixtures added with this revision. Reference: Section 103.2.3, UPC 2006. |
12/04/2008 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/08/2008 | SUE REEVES | OUT TO CUSTOMER | Completed |
12/08/2008 | SUE REEVES | REJECT SHELF | Completed |