Permit Number: T08CM02990
Parcel: 11901076A

Address:
3372 S 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02990
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 3372 S 6th Ave
T08CM02990
Building Plan (2nd Review)

TRANSMITTAL DATE: October 27, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved revised development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped development plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t08cm02990.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
10/27/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The two sets of roof drains/overflows located at column lines 5.5 and 7 are undersized based on the minimum requirements of Section 1106.0, UPC 2006.
10/27/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/28/2008 GERRY KOZIOL WWM REVIEW Denied 1:EL SUPER- ISSUED WITH GREASE INTERCEPTOR- NEED WASTEWATER IWC REVIEW & APPROVAL- TOM TOMCHAK 5025 W INA RD- 443-6200
2:NEED TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER - NEED DEQ REVIEW & APPROVAL TO CONSTRUCT ON-SITE PRIVATE SEWER IF OVER 3000 GAL/DAY- 740-3340
3: NEED ADDRESSING REVIEW - 740-6480- if not already done

Final Status

Task End Date Reviewer's Name Type of Review Description
11/03/2008 CPIERCE1 OUT TO CUSTOMER Completed
11/03/2008 SUE REEVES REJECT SHELF Completed