Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08CM02990
Parcel: 11901076A

Address:
3372 S 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02990
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2008 DAVE MANN FIRE REVIEW Approved
10/09/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/16/2008 GERRY KOZIOL WWM REVIEW Denied 1:EL SUPER- ISSUED WITH GREASE INTERCEPTOR- NEED WASTEWATER IWC REVIEW & APPROVAL- TOM TOMCHAK 5025 W INA RD- 443-6200
2:NEED TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER - NEED DEQ REVIEW & APPROVAL TO CONSTRUCT ON-SITE PRIVATE SEWER IF OVER 3000 GAL/DAY- 740-3340
3: NEED ADDRESSING REVIEW - 740-6480
10/17/2008 ROBERT SHERRY WATER REVIEW Approved
10/17/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the envelope energy calculation to use Pima County, less than 4,000 feet, not Marana.
2. Modify the drawings as required to correlate to the envelope energy calculation.
10/17/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Determine which plumbing code is to be used; IPC or UPC.
2. Correct the roof drainage calculations to use the correct rainfall amount (3"/HR) and the correct plumbing code.
3. Revise the detail sheet to show what is being built: the scuppers have been eliminated.
4. The roof drains shall not terminate over the sidewalk. The overflow drains may terminate as shown in detail 21/A8.0.
5. 2-way cleanouts shall be a listed fitting (singular), not a field fabrication. Reference Sections 707.4 and 707.6, UPC 2006.
6.Submit the underground plumbing for review (not appropriate for walk-through review.
10/22/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 3372 S 6th Ave
T08CM02990
Building Plan (2nd Review)

TRANSMITTAL DATE: October 22, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved revised development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped development plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t08cm02990.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents

Final Status

Task End Date Reviewer's Name Type of Review Description
10/24/2008 VFLORES1 OUT TO CUSTOMER Completed
10/24/2008 SUE REEVES REJECT SHELF Completed