Review Details: POST 3RD PARTY REVIEW

Permit Number - T08CM02978
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2009 MARTIN BROWN FIRE REVIEW Denied Please include the following sprinkler design criteria to the plans. The rest can be a deferred submittal.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
03/13/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/17/2009 ROBERT SHERRY WATER REVIEW Approved
03/18/2009 GERRY KOZIOL WWM REVIEW Approved