Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM02968
Parcel: 141177160

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02968
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2008 STEVE SHIELDS ZONING REVIEW Approved
09/03/2008 LOREN MAKUS ENGINEERING REVIEW Approved
09/05/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
09/05/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations:
a. Coordinate the area descriptions with the floor plans
b. Show that the calculations for the multi-zone system comply with section 6.2.5, ASHRAE 62.1-2004
c. Identify the occupancy categories (Table 6-1) used to determine the required ventilation.
2. Provide shell package drawings with structural calculations to verify that the new heat pump can be supported on the roof.
09/05/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. REFER TABLE 2902.1 FOR REQUIRED PLUMBING FIXTURES. DRINKING FOUNTAIN REQUIRED.
2. LOCATE TOILET PAPER DISPENSER PER ICC/ANSI A117.1-2003, FIGURE 604.7.
09/05/2008 ROBERT SHERRY WATER REVIEW Denied Provide shell package drawings and information to show that a proper backflow preventer is in place and that the existing water meter is adequate to support the added water demand of this suite.
09/05/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Vertical wet venting is limited to 1- and 2-unit fixtures. The clothes washer is a 3-unit fixture. reference Section 908.1, UPC 2006.
09/05/2008 RBROWN1 ADA REVIEW Passed
09/05/2008 RONALD BROWN ZONING HC SITE REVIEW Denied 1. SEE BUILDING COMMENTS
09/18/2008 CPIERCE1 WWM REVIEW Needs Review
09/18/2008 CPIERCE1 FIRE REVIEW Needs Review
09/18/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review