Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02968
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/03/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
09/03/2008 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
09/05/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/05/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the ventilation calculations: a. Coordinate the area descriptions with the floor plans b. Show that the calculations for the multi-zone system comply with section 6.2.5, ASHRAE 62.1-2004 c. Identify the occupancy categories (Table 6-1) used to determine the required ventilation. 2. Provide shell package drawings with structural calculations to verify that the new heat pump can be supported on the roof. |
09/05/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. REFER TABLE 2902.1 FOR REQUIRED PLUMBING FIXTURES. DRINKING FOUNTAIN REQUIRED. 2. LOCATE TOILET PAPER DISPENSER PER ICC/ANSI A117.1-2003, FIGURE 604.7. |
09/05/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide shell package drawings and information to show that a proper backflow preventer is in place and that the existing water meter is adequate to support the added water demand of this suite. |
09/05/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Vertical wet venting is limited to 1- and 2-unit fixtures. The clothes washer is a 3-unit fixture. reference Section 908.1, UPC 2006. |
09/05/2008 | RBROWN1 | ADA | REVIEW | Passed | |
09/05/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Denied | 1. SEE BUILDING COMMENTS |
09/18/2008 | CPIERCE1 | WWM | REVIEW | Needs Review | |
09/18/2008 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
09/18/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |