Permit Number: T08CM02948
Parcel: 111053580

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02948
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2008 MARTIN BROWN FIRE REVIEW Approved
09/16/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/16/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/16/2008 ROBERT SHERRY WATER REVIEW Passed
09/23/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project:3522 E Presidio Rd
T08CM02948
Fire repair

Plan has been rejected for the following items,

1. The existing service appeared to be 90 amps.Also the service appeared to be part of a four plex service on one on it's own as shown.Show as on site.
2. Panel location is required to be on plan not left to installer so compliance to code cann be confirmed.
3. Provide a load calculation per code.

Ray T Majuta
DSD City of Tucson
Electrical Plan Check
520-837-4988
9/24/08
09/26/2008 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/06/2008 GERARDO BONILLA OUT TO CUSTOMER Completed