Permit Number: T08CM02938
Parcel: 11016223A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02938
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2008 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
11/05/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/12/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Deferral of the design for the mounting shelf for the water heater requires the approval of the building official prior to approval of the construction documents. Reference: Section 106.3.4.2, IBC 2006.
2. Comment not resolved. Provide material standards for all plumbing fixtures being provided by others. For example, water closets shall be listed and labeled by a nationally recognized 3rd party listing agency as conforming to the approved applicable standards referenced in Chapter 14, UPC 2006 (e.g. ASME A112.19.2M-2003). Reference: Sections 301.1 and 401.1, UPC 2006.
3. Comment not addressed. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. (Note that the 2006 IECC has only 6 chapters.)
4. Comment not addressed. Provide a vacuum relief for water heater WH-1. Reference: Section 608.7, UPC 2006.
11/13/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/24/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/11/2008 CPIERCE1 OUT TO CUSTOMER Completed
12/11/2008 SUE REEVES REJECT SHELF Completed