| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/02/2008 | DAVE MANN | FIRE | REVIEW | Denied | Fire sprinklers are required for the canopy. The main structural members are wood (columns and GLB's). It also appears there will be seating or sales under the canopy. |
| 09/02/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/15/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET S1.1; CALCULATIONS: THE CALCULATIONS INDICATE A HSS3X2X1/8 FOR BEAM B1, WHILE THE PLAN INDICATES A HSS2X2X1/8. CLARIFY. 2. SHEET S1.1; CALCULATIONS: THE CALCULATIONS INDICATE (2) HSS2.5X2.5X1/8 FOR BEAM B3, WHILE THE PLAN INDICATES (2) HSS2X2X1/8. CLARIFY. 3. SPECIAL INSPECTIONS CERTIFICATE: DAVID P. LUNENG IS NOT ON THE CITY OF TUCSON'S LIST OF APPROVED SPECIAL INSPECTORS. MR. LUNENG MAY APPLY TO BE INSTATED ON THIS LIST BY SENDING AN INTRODUCTION LETTER, WORK RESUME, AND A LIST OF LICENSES AND CERTIFICATIONS TO THE BUILDING OFFICIAL, JESSIE SANDERS, AT P.O. BOX 27210, TUCSON, AZ., 85726, AND AWAIT MR. SANDER'S DECISION. AS AN ALTERNATIVE, USE A TESTING LABORATORY THAT EMPLOYS INDIVIDUALS CERTIFIED AS SPECIAL INSPECTORS AND RECOGNIZED BY THE CITY OF TUCSON. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/07/2008 | VFLORES1 | OUT TO CUSTOMER | Completed |
| 10/07/2008 | SUE REEVES | REJECT SHELF | Completed |