Permit Number: T08CM02937
Parcel: 11618348C

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T08CM02937
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2008 DAVE MANN FIRE REVIEW Denied Fire sprinklers are required for the canopy. The main structural members are wood (columns and GLB's).

It also appears there will be seating or sales under the canopy.
09/02/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/15/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1.1; CALCULATIONS: THE CALCULATIONS INDICATE A HSS3X2X1/8 FOR BEAM B1, WHILE THE PLAN INDICATES A HSS2X2X1/8. CLARIFY.
2. SHEET S1.1; CALCULATIONS: THE CALCULATIONS INDICATE (2) HSS2.5X2.5X1/8 FOR BEAM B3, WHILE THE PLAN INDICATES (2) HSS2X2X1/8. CLARIFY.
3. SPECIAL INSPECTIONS CERTIFICATE: DAVID P. LUNENG IS NOT ON THE CITY OF TUCSON'S LIST OF APPROVED SPECIAL INSPECTORS. MR. LUNENG MAY APPLY TO BE INSTATED ON THIS LIST BY SENDING AN INTRODUCTION LETTER, WORK RESUME, AND A LIST OF LICENSES AND CERTIFICATIONS TO THE BUILDING OFFICIAL, JESSIE SANDERS, AT P.O. BOX 27210, TUCSON, AZ., 85726, AND AWAIT MR. SANDER'S DECISION. AS AN ALTERNATIVE, USE A TESTING LABORATORY THAT EMPLOYS INDIVIDUALS CERTIFIED AS SPECIAL INSPECTORS AND RECOGNIZED BY THE CITY OF TUCSON.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/07/2008 VFLORES1 OUT TO CUSTOMER Completed
10/07/2008 SUE REEVES REJECT SHELF Completed