Permit Number: T08CM02934
Parcel: 131031690

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM02934
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2008 GERRY KOZIOL WWM REVIEW Approved needs 5th floor credit evaluation
10/01/2008 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T08CM02934

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

GENERAL NOTES:

" All code references to the International Residential Code shall be changed from 2003 to 2006 with appropriate paragraph references. Revise code references sheet 7 & 8.
" Provide legible plans with clear notation (minimum 1/8" lettering). Provide definite contrast of all portions of each character.
" Remove all revision markings. The approved plans do not have revised changes.

STRUCTURAL PLANS:

1. Verify the existing lintel sizes for carrying the new roof loads, R301.1.

SECTIONS - DETAILS:

1. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2.
2. Specify water-resistive barrier equivalent to two layers of Grade D paper over the wood based sheathing of exterior plaster wall coverings, R703.6.3.
3. Show location and method of flashing all wall and roof intersections, R903.2.1.

PLUMBING PLANS:

1. Provide water hammer arresters wherever quick-closing valves are installed in a water distribution system. The devices should conform to ASSE 1010-2004. Water hammer arresters are required for the clothes washer water connections, IRC P2903.5.
2. Provide water pressure range, developed length, and diameter of water lines between the meter to the furthest fixture, IRC P2903.7.
3. Provide a fixture unit schedule (to include existing fixtures) for determining required service pipe size, IRC P2903.6. Consider upgrading the supply pipe size between the meter and water heater.
4. Show the relocated gas service pipe. Any underground gas piping beneath buildings shall be encased in an approved sealed & vented conduit, IRC G2415.11.
5. Provide gas pipe sizes in compliance with connected demand. IRC G2413.3 & Table G2413.4(1).

MECHANICAL PLANS:

1. Show supply and return ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, R1103.2.1. Show R-4.2 insulation when ducts are located in an unconditioned space (chase) inside the thermal envelope, IECC 503.2.7 (City of Tucson Amended).
2. Verify a means of room return air to the central register (undercut door, transfer grille), M1602.
3. Provide return air duct and register sizes, M1602. Minimum duct/register size: heat pump or air conditioner - 6 SQ IN / 1000 BTU, M1403.1 (1 ton cooling = 12,000 BTU).
4. Show the removal of the furnace or show compliance for combustion air requirements. Confined spaces require a minimum of two 100 SQ. IN. openings, M1702.2.

ELECTRICAL PLANS:

1. Specify recessed lighting with 3" separation from combustibles or IC listing, R808, and compliance with energy efficiency leakage, N1102.4.3.
2. Provide an electrical riser diagram, E3303. Note the grounding and bonding method, E3507. Metallic gas lines must be bonded and shall not be used as the primary grounding method, E3508.
3. Show circuit 12 on the panel schedule, E3304.11 & E3606.2.
4. Show the Panel Board as relocated, E3501.6.2 & E3605.8.
5. Show Bathroom equipment (tub motor) on a GFCI circuit , E3603.4.
6. Show a GFCI receptacle outlet on the same level within 25' of exterior HVAC equipment, E3801.11.
7. Note that combination type arc-fault circuit interrupter shall protect bedroom outlets including receptacles, lights and smoke detectors, E3802.12.
8. Indicate the location of all disconnect switches for air handling equipment, E4001.5.

OUTDOOR LIGHTING CODE

1. Provide cut sheets for all full cut-off fixtures showing the lamp placement and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style). Fixtures are only exempt from the total lumen budget if both of the full cut-off FCO style and located under overhangs, OLC 5.1.2. Or, show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.75, ceiling R=30 and walls R=13. Show the "U" factors of the windows and doors on the plans, N1101.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review