Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02927
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/29/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
08/29/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02927 8/29/08 1. Show all electrical equipment intended for the new panel, with specific circuits indicated. 2. Provide panel schedule, with load calculations, for new panel. 3. Provide fault current rating of new panel. 4. Provide TEP available fault current at the service. 5. Provide fault calculations for new panel. 6. Provide overcurrent protection for new panel. |
08/29/2008 | DAVE MANN | FIRE | REVIEW | Denied | Clarify what is happening with fire pump room. Are walls and doors changing. Show fire rating. |
09/02/2008 | VFLORES1 | ADA | REVIEW | Needs Review | |
09/02/2008 | VFLORES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
09/02/2008 | VFLORES1 | ZONING HC SITE | REVIEW | Needs Review |