Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM02927
Parcel: 12404100A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02927
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
08/29/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM02927 8/29/08

1. Show all electrical equipment intended for the new panel, with specific circuits indicated.
2. Provide panel schedule, with load calculations, for new panel.
3. Provide fault current rating of new panel.
4. Provide TEP available fault current at the service.
5. Provide fault calculations for new panel.
6. Provide overcurrent protection for new panel.
08/29/2008 DAVE MANN FIRE REVIEW Denied Clarify what is happening with fire pump room. Are walls and doors changing. Show fire rating.
09/02/2008 VFLORES1 ADA REVIEW Needs Review
09/02/2008 VFLORES1 BUILDING-COMMERCIAL REVIEW Needs Review
09/02/2008 VFLORES1 ZONING HC SITE REVIEW Needs Review