Permit Number: T08CM02922
Parcel: 13604328C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02922
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2008 DAVE MANN FIRE REVIEW Approved
09/03/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/03/2008 ENEWCOM1 ADA REVIEW Passed
09/03/2008 ROBERT SHERRY WATER REVIEW Approved
09/03/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/03/2008 LOREN MAKUS ENGINEERING REVIEW Approved
09/03/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/03/2008 DAVID RIVERA ZONING REVIEW Approved
09/03/2008 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
09/04/2008 GERRY KOZIOL WWM REVIEW Approved
09/04/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/04/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08CM02922 9/3/08

1. MOCP=40/45 according to Sheet M1. Electrical uses 45, which would correspond to an MCA of 42, or 17459VA, not 14213. Please coordinate with Mechanical and clarify which unit is actually being used at this location.
2. Please add the following note to the plans: "All work in patient care areas shall comply with NEC 517.13."