Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02922
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/29/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 09/03/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/03/2008 | ENEWCOM1 | ADA | REVIEW | Passed | |
| 09/03/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/03/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/03/2008 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 09/03/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/03/2008 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 09/03/2008 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
| 09/04/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/04/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/04/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T08CM02922 9/3/08 1. MOCP=40/45 according to Sheet M1. Electrical uses 45, which would correspond to an MCA of 42, or 17459VA, not 14213. Please coordinate with Mechanical and clarify which unit is actually being used at this location. 2. Please add the following note to the plans: "All work in patient care areas shall comply with NEC 517.13." |