Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Registrant shall sign and date seal for all sheets intended for inclusion in this project. Reference unnumbered sheet entitled "Site Plan."
2. On Keynote 9 on the 1-Line Diagram, please note that this location is not in Trico's service territory. In fact, this Keynote is not used on this project.
3. On the 1-Line Diagram, please extend the dashed line for Run B to include all three legs.
4. Provide specifications for the plaque required under NEC 690.56 (B), including EXACT WORDING as to the location of the respective power sources.