Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2008 GERRY KOZIOL WWM REVIEW Approved
09/22/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 9-22-08
Activity: T08CM02853
Address: 5208 N. Foothills Dr.
Applicant: Fast Permits

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

2. Correct drawing titles (North and East Elevation used on two drawings each).

FLOOR PLANS:
3. Specify safety glazing in hazardous locations (less than 60" above tub/shower floors), R308.4.

SECTIONS - DETAILS:
4. Provide detail for porch ledger connection to existing wall.

ELECTRICAL PLAN:
5. Use Table E3602.13 for sizing 15, 20 & 30 AMP branch circuit conductors.
6. Lights installed over a shower or bathtub must be approved for use in wet area, E3903.8.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review