Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM02849
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/29/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/06/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/07/2008 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
| 11/19/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the plumbing plans to include the added plumbing fixtures, including the schedules, water isometrics and waste and vent isometrics (sheet P.2). Reference: Section 103.2.3, UPC 2006. |
| 11/19/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Correct the arithmetic in the ventilation calculations. For HP-4: (1560 SF)*(15 people/1000 SF)*(16 CFM/person) = 374 CFM total ventilation required. 2. Provide plans (sheet S.1) sealed by an Arizona Registrant. (Replot to make the keynotes legible.) Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. |
| 11/19/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Verify the locations of the water meter and backflow preventer as shown on sheet C.1. Water meters are not normally located on private property. 2. Comment not addressed. Provide the total demand placed on the water meter. Reference: Section 103.2.3, UPC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/25/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 11/25/2008 | SUE REEVES | REJECT SHELF | Completed |