Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02849
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/22/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. 1/8" LETTERING ON ALL DRAWINGS REQUIRED UNLESS A WRITTEN APPEAL IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY DRAWINGS SUBMITTED FOR CHECKING. 2. SHEET T.1; CODE REVIEW: COMPLETE #10 (PLUMBING FIXTURES REQUIRED) INCLUDING WATER CLOSETS, LAVATORIES, DRINKING FOUNTAINS, AND SERVICE SINKS. REVISE PLANS AS REQUIRED. 3. ENLARGE BATHROOM PLANS TO 1/4" SCALE. INCLUDE CRITICAL DIMENSIONS PER ICC/ANSI A117.1-2003, CHAPTER 6. 4. IS PERMIT FOR CERTICATE OF OCCUPANCY, OR LETTER OF COMPLETION ONLY? VERIFY. |
| 08/22/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/22/2008 | RBROWN1 | ADA | REVIEW | Passed | NOT A COT PROJECT |
| 08/22/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/25/2008 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 09/03/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Provide the site utility plan showing the location of the reduced pressure backflow assembly on the drawings, specify the reduced pressure backflow assembly being installed, and indicate the size of the assembly. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf 2. Provide the size of the existing water meter and total demand placed on that meter. Reference: Section 103.2.3, UPC 2006. |
| 09/03/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006. 2. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for mercantile occupancy. |
| 09/03/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006. 2. Provide structural calculations and framing details to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top unit. Reference: Section 302.1, IMC 2006. 3. Show how adequate access is being provided for the equipment located on the roof. Reference: Section 306.5, IMC 2006. 4. Show that the termination of the condensate drain is located so that the direct connection to a tailpiece is in the same area controlled by the person controlling the air-conditioned space. Reference: Section 807.2, UPC 2006. 5. Correct the arithmetic in the ventilation calculations |
| 09/12/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | see coments for T08CM02840 |
| 09/18/2008 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/28/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 10/28/2008 | SUE REEVES | REJECT SHELF | Completed |