Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM02844
Parcel: 113030820

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02844
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/06/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/07/2008 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
11/19/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the plumbing plans to include the added plumbing fixtures, including the schedules, water isometrics and waste and vent isometrics (sheet P.2). Reference: Section 103.2.3, UPC 2006.
11/19/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Correct the arithmetic in the ventilation calculations. For HP-3: (1560 SF)*(15 people/1000 SF)*(16 CFM/person) = 374 CFM total ventilation required.
2. Provide plans (sheet S.1) sealed by an Arizona Registrant. (Replot to make the keynotes legible.) Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
11/19/2008 ROBERT SHERRY WATER REVIEW Denied 1. Verify the locations of the water meter and backflow preventer as shown on sheet C.1. Water meters are not normally located on private property.
2. Comment not addressed. Provide the total demand placed on the water meter. Reference: Section 103.2.3, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/25/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
11/25/2008 SUE REEVES REJECT SHELF Completed