Permit Number: T08CM02840
Parcel: 113030820

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02840
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. 1/8" LETTERING ON ALL DRAWINGS REQUIRED UNLESS A WRITTEN APPEAL IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY DRAWINGS SUBMITTED FOR CHECKING.
2. SHEET T.1; CODE REVIEW: COMPLETE #10 (PLUMBING FIXTURES REQUIRED) INCLUDING WATER CLOSETS, LAVATORIES, DRINKING FOUNTAINS, AND SERVICE SINKS. REVISE PLANS AS REQUIRED.
3. ENLARGE BATHROOM PLANS TO 1/4" SCALE. INCLUDE CRITICAL DIMENSIONS PER ICC/ANSI A117.1-2003, CHAPTER 6.
4. IS PERMIT FOR CERTICATE OF OCCUPANCY, OR LETTER OF COMPLETION ONLY? VERIFY.
08/22/2008 MARTIN BROWN FIRE REVIEW Approved
08/22/2008 RBROWN1 ADA REVIEW Passed NOT A COT PROJECT
08/22/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/25/2008 ERIC NEWCOMB ZONING HC SITE REVIEW Denied 1. SEE BUILDING COMMENTS
09/03/2008 ROBERT SHERRY WATER REVIEW Denied 1. Provide the site utility plan showing the location of the reduced pressure backflow assembly on the drawings, specify the reduced pressure backflow assembly being installed, and indicate the size of the assembly. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
2. Provide the size of the existing water meter and total demand placed on that meter. Reference: Section 103.2.3, UPC 2006.
09/03/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for mercantile occupancy.
09/03/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Revise the termination of the condensate drain so that the location of the direct connection to a tailpiece is in the same area controlled by the person controlling the air-conditioned space. Reference: Section 807.2, UPC 2006.
3. Provide structural calculations and framing details to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top unit. Reference: Section 302.1, IMC 2006.
4. Show how adequate access is being provided for the equipment located on the roof. Reference: Section 306.5, IMC 2006.
5. Correct the arithmetic in the ventilation calculations
09/12/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT; 3650 N 1ST
T08CM02840 #100
T08CM02840 #110
T08CM02849 #120
T08CM02850 #130

These projects have been denied for the following,

1.The electrical sheets are required to all be signed by the electrical engineer and dated.
2. Provide fault current calculations starting at the service on to the panels.
3. Conductor feeds to the new 1000 amp CT can do not show the grounded conductor.
4. Service disconnects showing units 100,124,126,128, are incorrect, show 100,110,120,130, as labeled on permit.
5. Conductors going to main service disconnects do not show grounded conductors.
6. Label panels according to suite numbers not letters.
7. Provide rooftop service receptacles for Hvac equipment.
8. Describr fixture C type and show to which panel and circuit it will be going to.


Ray T Majuta
DSD City of Tucson,
Plan Check.
9/15/08