Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM02831
Parcel: 13327001B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02831
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
08/21/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/21/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Clarify Keynotes 3 and 4 on Power Plan.
08/21/2008 ROBERT SHERRY WATER REVIEW Approved
08/21/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/21/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify how the water temperature is to be controlled at the lavatories; two mixing valves appear to be specified.
2. Provide a cleanout for the existing 4" grease waste being connected to the new hand sink (4" lines require a minimum of 3-1/2" cleanouts).
3. Show the location of the new floor sink on the plumbing plan.
4. Correct the size of the waste line for the new hand sink and floor sink on the riser diagram.
08/21/2008 ENEWCOM1 ADA REVIEW Passed
08/21/2008 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
08/26/2008 CPIERCE1 WWM REVIEW Needs Review
08/26/2008 CPIERCE1 FIRE REVIEW Needs Review
08/26/2008 CPIERCE1 ENGINEERING REVIEW Needs Review
08/26/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review