Permit Number: T08CM02805
Parcel: 12307229B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02805
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide CW shut off valves for each building entrance. Reference: Section 605.2, UPC 2006.
2. Comment not resolved. The note "Based upon shell bldg engineer's calculations…" is not applicable since there are no shell building plans and the architect does not include any plumbing drawings in his drawing set. Provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006.
12/05/2008 TERRY STEVENS ZONING REVIEW Approved
12/05/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/12/2008 THAUSER1 OUT TO CUSTOMER Completed
12/12/2008 SUE REEVES REJECT SHELF Completed