Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM02804
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved. The note "Based upon shell bldg engineer's calculations…" is not applicable since there are no shell building plans and the architect does not include any plumbing drawings in his drawing set. Provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006. 2. Comment not resolved. Include the four hose bibbs in the water demand calculations. Reference: Section 610.1, UPC 2006. 3. Coordinate detail 208/P2.1 with detail 102/M-2. |
| 12/05/2008 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 12/05/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/12/2008 | THAUSER1 | OUT TO CUSTOMER | Completed |
| 12/12/2008 | SUE REEVES | REJECT SHELF | Completed |