Permit Number: T08CM02798
Parcel: 125051210

Address:
2221 E 5TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02798
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 11-04-09
Activity: T09CM02798
Address: 2221 E. 5th St
Applicant: Rodney Mackey

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

ELECTRICAL PLAN:
2. Exterior receptacles may not share the bathroom circuit, E3801.6.

INTERNATIONAL ENERGY CONSERVATION CODE:
3. Tucson is in climate zone 2B. The simplified prescribed energy values for ceiling spaces is R=30, N1102.1. Provide for the minimum required ceiling insulation or provide an energy calculation for the U-factor of the entire structure in compliance with the Department of Energy. Note: standard R-30 batt insulation requires at least 9.5" of cavity space.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/20/2009 CPIERCE1 OUT TO CUSTOMER Completed
11/20/2009 SUE REEVES REJECT SHELF Completed