Review Details: RESUBMITTAL

Permit Number - T08CM02792
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. 1/8" LETTERING ON ALL DRAWINGS REQUIRED UNLESS A WRITTEN APPEAL IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY DRAWINGS SUBMITTED FOR CHECKING. REFERENCE ARCHITECTURAL AND STRUCTURAL DRAWINGS. PLEASE PROVIDE AN APPROVED BUILDING OFFICAL APPEAL APPROVAL.
2. ALL DEFERRED SUBMITTALS MUST BE APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVAL MUST ACCOMPANY DRAWINGS SUBMITTED FOR CHECKING. REFERENCE PLATED WOOD TRUSSES.
3. SHEET A.4; SECTIONS 1, 3 AND 4: FOR DETAILS 3 AND 4: TRUSS CONNECTION CAN NOT BE DIRECTLY TO WEB. CONNECT TOP OR BOTTOM CORD WITH BRACING AND CONNECT WALL BRACING TO TOP OR BOTTOM CORD.
FOR DETAIL 1: PROVIDE 2X4 WEB BRACING AT EACH FASCIA AND CEILING FRAMING CONNECTION. DIRECT WEB ATTACHMENT IS NOT ACCEPTABLE BY MANUFACTURER.
3. DENOTE ASSURANCE THAT SERVICE COUNTER WILL HAVE AN ACCESSIBLE COUINTER SECTION.
12/18/2008 STEVE SHIELDS ZONING REVIEW Approved
12/19/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/19/2008 ROBERT SHERRY WATER REVIEW Denied Comment not addressed. Provide a letter from Tucson Water confirming that the use of a 5/8" water meter will be allowed for this project (24.5 fixture units equates to a demand of 17 GPM).
12/19/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/19/2008 LOREN MAKUS ENGINEERING REVIEW Approved DATE: December 19, 2008
SUBJECT: Site Plan
TO: KBP Architecture LLC
LOCATION: 7865 E Speedway Blvd, T13S, R14E, Sec 30
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T08CM02792 (First Review)

1. Need Floodplain Use Permit to be submitted along with next submittal of Building Permit.

2. Include copy of Drainage Report with established minimum finished floor elevation for proposed restaurant.

3. Unable to approved Building Permit until all Floodplain Use requirements have been met.

4. Additional comments may be forthcoming.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax
12/19/2008 LOREN MAKUS ENGINEERING REVIEW Approved Based on further review, this building permit is approved.
12/22/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The revised waste and vent riser diagram appears to show a 2" vent located between the air intake for the flow control device and the hydromechanical grease interceptor. Revise the drawing to comply with the requirements of Section 1014.2.1, UPC 2006.
2. The scupper sizing calculations provided for the north and south roof areas appear to have been done using the 2003 UPC which does not meet the requirements of the 2006 UPC. In addition, the projected area of the north roof area is smaller than shown on the plans and neither area calculation includes the effect of the surrounding parapets. Reference: Sections 1101.11.1, 1101.11.2.1, and 1106.4, UPC 2006, and Section 1611.1, IBC 2006.
3. The scupper sizing calculations provided for the center roof area appears to have been done using the 2003 UPC which does not meet the requirements of the 2006 UPC. In addition, the area calculation does not include the effect of the surrounding walls and parapets. Reference: Sections 1101.11.1, 1101.11.2.1, and 1106.4, UPC 2006, and Section 1611.1, IBC 2006.
12/23/2008 GERRY KOZIOL WWM REVIEW Denied 1)EL POTPSINO RESTAURANT- ISSUED W/ GREASE INTERCEPTOR
2)REPLACEMENT PROJECT- NEEDS WASTEWATER CREDIT REVIEW FOR PREV ISSUED PERMITS PT07S01081 & PT07S01082
3)NEEDS WWM 3RD FLOOR REVIEW/ILENE DECKARD REVIEW OF EASEMENTS USE AGREEMENTS DKT 12588 PG 1535
4)NEED WWM 3RD FLOOR MANHOLE TAP REVIEW & PERMIT/ YVONNE SUAREZ
12/23/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations for the building envelope. The calculations shall be for "Pima County < 4,000 feet", not the town of Pima, Arizona. Reference: Section 101.4, International Energy Conservation Code 2006.
2. Provide structural calculations for the connection of the 4"x8" wood beam to the roof framing (Detail 2/A.4). The submitted calculations cover the ΒΌ" bent plate hanger for the threaded rod but not the connection of the 4"x8" beam. Reference: Section 302.1, IMC 2006.
12/29/2008 JEFF DRUMM LANDFILL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/21/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
01/21/2009 SUE REEVES REJECT SHELF Completed