Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM02778
Parcel: 141176860

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02778
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2008 MARTIN BROWN FIRE REVIEW Approved
10/30/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/03/2008 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
11/04/2008 GERRY KOZIOL WWM REVIEW Approved
11/06/2008 STEVE SHIELDS ZONING REVIEW Approved
11/13/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved, revised drawings not provided. The specified water heater (Ruud ES120) has a shell diameter of 30.25" and the distance from the front of the control panel to the opposite side of the water heater is 36". The water heater must pass through an opening only 2'-4" wide and operate in a space only 3'-2" x 4'-0". Considering the manufacturer requires a minimum of 18" clearance from the control panel to combustible construction with additional space allowed for inspection and servicing, the planned installation appears to be at odds with the manufacturer's requirements. Provide access and working space for the water heater. Reference: Section 505.3, UPC 2006.
2. Comment not resolved, revised drawings not provided. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.
11/13/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the architectural detail 23/A9.10 to show how the all-thread hangers are being suspended from the wood I-joists. Reference: Section 302.1, IMC 2006.
2. Revised drawings not supplied, comment not resolved; see AC-1 and AC-3, AC-4 and AC-6. Combining two AC units of any size requires a minimum drain size of 1". Provide information to show how the condensate drains serving multiple fan coils have been sized. Reference: Section 307.2.2, IMC 2006, as amended by the City of Tucson.
11/13/2008 ROBERT SHERRY WATER REVIEW Approved
11/14/2008 SREEVES1 ELECTRICAL-COMMERCIAL REVIEW Passed approved last review