Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM02774
Parcel: 11615088L

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02774
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2008 STEVE SHIELDS ZONING REVIEW Approved
08/14/2008 JASON GREEN ENGINEERING REVIEW Needs Review FUP required due to A Zone.
08/15/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM02774 8/15/08

1. Provide panel and circuit for receptacles in ECHO VASCULAR.
2. Provide load calculations for Panel L2AR.
3. It is not clear why electrical load calculations have been performed for Panel L2AL, since no electrical load appears to be added to the panel.
4. Account for Panel L2AR on One Line Diagram.
5. L2AL is show twice on One Line.
6. Print on load calculations has overwrites.
08/15/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/15/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/15/2008 ROBERT SHERRY WATER REVIEW Approved
08/15/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/15/2008 RBROWN1 ADA REVIEW Passed
08/15/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
09/02/2008 DROBEY1 WWM REVIEW Needs Review
09/02/2008 DROBEY1 FIRE REVIEW Needs Review
09/02/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/02/2008 DELMA ROBEY OUT TO CUSTOMER Completed