Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08CM02770
Parcel: 14111002B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02770
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2008 TERRY STEVENS ZONING REVIEW Approved
08/15/2008 MARTIN BROWN FIRE REVIEW Approved
08/18/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review Impact Fee's Do Apply; Southeast District; 1,800 Square foot building; $3,813
08/21/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide site drawing showing the size and route of the building water supply along with the locations of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006.
2. Comment not addressed. According to Tucson water, this location will receive higher than normal water pressure. Show how the water pressure will be limited to less than 80 PSI, Reference: Section 608.2, UPC 2006.
3. Comment not addressed. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
08/21/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide sufficient heat for the workshop/warehouse area to maintain a minimum temperature of 68 F on a design heating day (32 F). Reference: Section 309.1, IMC 2006.
2. Comment not addressed. Provide calculations demonstrating adequate ventilation. Reference: Section 401.2, IMC 2006.
11/04/2008 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/04/2008 DELMA ROBEY APPROVAL SHELF Completed
11/04/2008 DELMA ROBEY OUT TO CUSTOMER Completed
11/04/2008 DELMA ROBEY REJECT SHELF Completed