Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM02770
Parcel: 14111002B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02770
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2008 VFLORES1 ZONING REVIEW Needs Review
08/14/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide sufficient heat for the workshop/warehouse area to maintain a minimum temperature of 68 F on a design heating day (32 F). Reference: Section 309.1, IMC 2006
2. Provide calculations demonstrating adequate ventilation. Reference: Section 401.2, IMC 2006.
08/14/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/14/2008 ROBERT SHERRY WATER REVIEW Approved
08/14/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/14/2008 GERRY KOZIOL WWM REVIEW Approved
08/14/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide site drawing showing the size and route of the building water supply along with the locations of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006.
2. According to Tucson water, this location will receive higher than normal water pressure. Show how the water pressure will be limited to less than 80 PSI, Reference: Section 608.2, UPC 2006.
3. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006
08/14/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
08/14/2008 VFLORES1 FIRE REVIEW Needs Review
08/14/2008 RBROWN1 ADA REVIEW Passed
08/14/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/14/2008 RONALD BROWN ZONING HC SITE REVIEW Approved