Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SITE ALL
Permit Number - T08CM02748
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/23/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Denied | Comments Item 4 states there are no marked crossings on the project. Please reference new marked crossing added to plan. This is not a code requirement but if so retained please add in detetcable warnings as per 2006 IBC/ICC-ANSI, Sections 406.12 and 406.14. |
| 10/24/2008 | TERRY STEVENS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Terry Stevens Lead Planner PROJECT: T08CM02748 3231 N. Freeway Industrial Loop Site Plan TRANSMITTAL DATE: 8/28/08 COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. DS 2-02.2.1.4 The following information has not bee provided in the location map. a. Identify conditions within the square mile area, such as major streets and watercourses. For example: I-10, the railroad, Ft. Lowell Rd.,etc. b. Remove Romero Rd from the south west corner of the location map. 2.. DS 2-02.2.1.12 The crosswalk leading to the north property line where it is located between the two vehicular parking spaces is required to be a physically separated sidewalk with a handicap ramp at the rear of the parking space. 3. The above comments are minor in nature and can be approved by setting an appointment with me for an over the counter review. If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961 C:\planning\cdrc\DSD\T08CM02748-2.doc |
| 10/27/2008 | DAVE MANN | FIRE | REVIEW | Denied | Confirm with user that no storage above 12' AFF is acceptable. The building is 21' tall, seems like a lot of wasted space. Installation of fire sprinklers would greatly increase flexibilty of use of building. Also, the occupancy load data on sheet A1.0 indicates a S-1 storage area of 14,363 sq. ft. Is there a mezzanine planned? Per Section 702 of the IBC, mezzanine counts as part of the fire area, which would seem to indicate fire sprinkler would be required. Please clarify. |
| 10/28/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Denied | DATE: October 29, 2008 SUBJECT: Site Plan TO: MPE LOCATION: 3231 N Freeway, T13S, R13E, Section 27, Ward 1 REVIEWERS: Bianca Ramirez, CFM ACTIVITY: T08CM02248 (Second Review) RESUBMITTAL REQUIRED: Site Plan SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal. Please include a response letter to the comments along with the corrected copies of the Site Plan. Site Plan: 1. Complied 2. Complied 3. Complied 4. Complied 5. Ensure that dimensioned maneuvering area(s) per D.S. 2-02.2.1.14. DS Sec.2-02.2.1.A.14: do not intercept curbing or sidewalk. Labeled and dimensioned radii appear to be going though sidewalk and curbing area. Please revise accordingly. 6. Complied 7. DS Sec.2.02.2.1.A.16: Provide drainage arrows for roof drainage and provide locations of all concentration points. Specifically show roof down spout locations proposed buildings at pedestrian circulation areas. A detail for the dimension of the proposed scuppers that are used for collecting onsite roof drainage at all pedestrian sidewalk is required, refer to City of Tucson details. Any scuppers proposed under the sidewalk will be designed and constructed to convey the 10-year flood flow. Provide a drainage statement showing scupper calculations and provide recommendations, which demonstrate that the 10-year flood flow is contained under the sidewalk. 8. Complied 9. Complied 10. Complied 11. Complied 12. Complied 13. Verify that contour lines are labeled and depicted accurately see site plan for reference per D.S. 2-02.2.1.23. 14. Provide contour interval on plan. Indicate by providing CI = 1' below scale and north arrow. 15. Complied 16. Complied 17. Verify that the trash enclosure meets the minimum requirements as illustrated on City of Tucson Solid Waste Disposal Detail. Include inside dimension in detail per D.S. 2-02.2.1.32 and D.S. 6-01.0. 18. Complied 19. Complied 20. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information. 21. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable. Please include information on site plan. 22. Complied 23. Add note: "Depress all landscaped areas 6" maximum for water harvesting". Please revise note: replace the word retention to harvesting. 24. Complied 25. "A grading permit will be required for this project. Submit 3 sets of grading with text, upon completion and submittal of a grading permit application. A grading permit may not be issued prior to site plan approval. Subsequent comments may be necessary, depending upon the nature and extent of revisions that occur to the plans". 26. Complied 27. Complied 28. Complied 29. Provide note along drainage easment where rip rap is indicated and provide opening and detail. 30. Check leader for note (6) and revise accordingly. See site plan for reference. 31. Revise SVT's to start at the edge of the SVT to be at the edge of curb. 32. Northeast corner of building there depicts Rail leaders leading to scupper. Provide explination or detail to depicte this area. 33. Change handicap sign to read $532 FINE within all appropriate details. 34 Provide section for drainage easement. 35. Additional comments may be forthcoming. If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov Bianca C. Ramirez Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 837-4928 office (520) 879-8010 fax |
| 11/06/2008 | VFLORES1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 11/06/2008 | VFLORES1 | LANDSCAPE | REVIEW | Needs Review |