Permit Number: T08CM02730
Parcel: 11012007B

Address:
5151 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM02730
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2008 VFLORES1 ZONING HC SITE REVIEW Needs Review
08/08/2008 VFLORES1 WWM REVIEW Needs Review
08/08/2008 VFLORES1 PLUMBING-COMMERCIAL REVIEW Needs Review
08/08/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/08/2008 VFLORES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/08/2008 VFLORES1 WATER REVIEW Needs Review
08/08/2008 VFLORES1 MECHANICAL-COMMERCIAL REVIEW Needs Review
08/08/2008 RBROWN1 ADA REVIEW Passed
08/11/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PER IBC 3409.7, GIVE A COST BREAKDOWN OF THE PROJECT, INDICATING COST OF ACCESSIBILITY ALTERATIONS (MAXIMUM REQUIREMENT OF 20%).
2. SHEET A1.0; FLOOR PLAN: PER IBC SECTION 3409.8.5 AND SECTION 1010.2, ACCESSIBLE EGRESS RAMP SLOPE WILL NOT EXCEED 12.5%. RAMP SLOPE INDICATED AT 17.88%. REVISE AS REQUIRED.
3. SHEET A1.0; FLOOR PLAN: NOTE TO 'FIELD VERIFY RAMP FOR ACCESSIBILITY....' MUST BE VERIFIED ON THESE DOCUMENTS.
4. SHEET A3.1: REMOVE NEW WALL/NEW PARTIAL WALL LEGENDS FROM SHEET.