Permit Number: T08CM02729
Parcel: 113061940

Address:
2326 E LIND RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM02729
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2008 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T08CM02729

10/23/08 2326 E. LIND RD.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

STRUCTURAL PLANS:

1. A CROSS SECTION OF THE A/C IN THE ATTIC WOULD OFFER AN OPPORTUNITY TO SHOW AND DIMENSION THE WORKING SPACE AND 22" (MIN.)WIDE CAT WALK REQUIRED BY M1305.1.3 AND TO SEE IF THE DUCT WORK WOULD CONFLICT WITH THE WORKING SPACE. LOOKING AT THE MECHANICAL PLAN, THE DUCT DOES APPEAR TO CONFLICT WITH THE WORKING SPACE. IS THERE ADEQUATE ROOM AROUND THE A/C THAT CLOSE TO THE LOWEST PART OF THE ROOF? ALSO, PLEASE MAKE MENTION OF THE SWITCHED LIGHT AND THE RECEPTACLE REQUIRED BY M1305.1.3.1 AND SHOW THEM ON THE ELECTRICAL PLAN.

SECTIONS - DETAILS - MISC. NOTES:

1. "TC24" vs "TC26" , ONE IS FOR A 2X4 WALL AND THE OTHER IS FOR A 2X6 WALL. 4,5/7 INDICATE A 2X6 WALL , 3,7/7 INDICATE 2X4 WALL. MY MISTAKE IN ASKING ABOUT THE TC IN 3/7. I SHOULD HAVE MENTIONED A DETAIL WITH 2X6 WALL. ANYWAY, WHAT WILL THE WALLS BE? 2X4 OR 2X6?

2. PROVIDE A CROSS SECTION OF THE WALL CLOSING THE GARAGE DOOR. WHAT WILL BE THE WALL COVERING BE. IF STUCCO, WILL THE WEEP SCREED BE 2" ABOVE PAVEMENT, 4" ABOVE EARTH ( R703.6.2.1 ) OR WILL THE WOOD BE 6" ABOVE THE GROUND (R319.1 ITEM 5)? HOW WILL THE BOTTOM PLATE BE CONNECTED TO THE CONCRETE?

3. BWP A / 4 ; PLEASE USE 16d NAILS NOT 16d SCREWS FOR THE HOLD DOWNS.


PLUMBING PLANS:

1. THE WATER SERVICE LINE FROM THE WATER METER TO THE "T" THAT SERVES THE GARAGE BATH ROOM SUPPLIES THE EXISTING PLUMBING FIXTURES AND THE ADDED GARAGE BATH ROOM. THIS LINE SHOULD CARRY THE FIXTURE UNITS OF THE HOUSE PLUS THE WATER FIXTURE UNITS OF THE NEW BATH ROOM AND MIGHT NEED TO BE INCREASED IN DIAMETER. MARY, 791-2658, @ TUCSON WATER CAN GET YOU AN ACCURATE WATER PRESSURE RANGE. ADD THE ITEMIZED WATER FIXTURE UNITS AND THE PROPOSED W.F.U. TO GET THE TOTAL THAT THE FIRST LENGTH OF PIPE FROM THE METER MUST DELIVER.



ELECTRICAL PLANS:

1. PROVIDE/IDENTIFY THE CIRCUIT TO THE RECEPTACLE AT THE GARAGE BATH ROOM'S LAVATORY. E3603.4 .



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 837-4910




PLAN CHECK COMMENTS - PROJECT #T08CM02729

10/23/08 2326 E. LIND RD.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

STRUCTURAL PLANS:

1. A CROSS SECTION OF THE A/C IN THE ATTIC WOULD OFFER AN OPPORTUNITY TO SHOW AND DIMENSION THE WORKING SPACE AND 22" (MIN.)WIDE CAT WALK REQUIRED BY M1305.1.3 AND TO SEE IF THE DUCT WORK WOULD CONFLICT WITH THE WORKING SPACE. LOOKING AT THE MECHANICAL PLAN, THE DUCT DOES APPEAR TO CONFLICT WITH THE WORKING SPACE. IS THERE ADEQUATE ROOM AROUND THE A/C THAT CLOSE TO THE LOWEST PART OF THE ROOF? ALSO, PLEASE MAKE MENTION OF THE SWITCHED LIGHT AND THE RECEPTACLE REQUIRED BY M1305.1.3.1 AND SHOW THEM ON THE ELECTRICAL PLAN.

SECTIONS - DETAILS - MISC. NOTES:

1. "TC24" vs "TC26" , ONE IS FOR A 2X4 WALL AND THE OTHER IS FOR A 2X6 WALL. 4,5/7 INDICATE A 2X6 WALL , 3,7/7 INDICATE 2X4 WALL. MY MISTAKE IN ASKING ABOUT THE TC IN 3/7. I SHOULD HAVE MENTIONED A DETAIL WITH 2X6 WALL. ANYWAY, WHAT WILL THE WALLS BE? 2X4 OR 2X6?

2. PROVIDE A CROSS SECTION OF THE WALL CLOSING THE GARAGE DOOR. WHAT WILL BE THE WALL COVERING BE. IF STUCCO, WILL THE WEEP SCREED BE 2" ABOVE PAVEMENT, 4" ABOVE EARTH ( R703.6.2.1 ) OR WILL THE WOOD BE 6" ABOVE THE GROUND (R319.1 ITEM 5)? HOW WILL THE BOTTOM PLATE BE CONNECTED TO THE CONCRETE?

3. BWP A / 4 ; PLEASE USE 16d NAILS NOT 16d SCREWS FOR THE HOLD DOWNS.


PLUMBING PLANS:

1. THE WATER SERVICE LINE FROM THE WATER METER TO THE "T" THAT SERVES THE GARAGE BATH ROOM SUPPLIES THE EXISTING PLUMBING FIXTURES AND THE ADDED GARAGE BATH ROOM. THIS LINE SHOULD CARRY THE FIXTURE UNITS OF THE HOUSE PLUS THE WATER FIXTURE UNITS OF THE NEW BATH ROOM AND MIGHT NEED TO BE INCREASED IN DIAMETER. MARY, 791-2658, @ TUCSON WATER CAN GET YOU AN ACCURATE WATER PRESSURE RANGE. ADD THE ITEMIZED WATER FIXTURE UNITS AND THE PROPOSED W.F.U. TO GET THE TOTAL THAT THE FIRST LENGTH OF PIPE FROM THE METER MUST DELIVER.



ELECTRICAL PLANS:

1. PROVIDE/IDENTIFY THE CIRCUIT TO THE RECEPTACLE AT THE GARAGE BATH ROOM'S LAVATORY. E3603.4 .



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 837-4910

Final Status

Task End Date Reviewer's Name Type of Review Description
10/29/2008 VFLORES1 OUT TO CUSTOMER Completed
10/29/2008 SUE REEVES REJECT SHELF Completed